Cooling Tower: Relative Plan Area (RPA) and Relative Power Consumption (RPC) with respect to Relative Cooling Capacity (RCC)


The following graph illustrates the relationship between the Relative Plan Area (RPA) and Relative Power Consumption (RPC) with respect to increasing Relative Cooling Capacity (RCC), and describes how to double the relative cooling capacity with the same values of all other thermal and size conditions.

RCC
RPA
RPC
1
1.00
1.00
1.1
1.15
1.33
1.2
1.31
1.73
1.3
1.48
2.20
1.4
1.66
2.74
1.5
1.84
3.38
1.6
2.02
4.10
1.7
2.22
4.91
1.8
2.41
5.83
1.9
2.62
6.86
2
2.83
8.00






In order to double the capacity (Relative Cooling Capacity) with the same values of all
other thermal and size conditions, the following must be done:
  • Increase the surface of the tower by 2 ^ 1.5 times, that is, 2 (double) to the power of 1.5 = 2.83. 
     The tower must be 2.83 times bigger with the same fan, air flow capacity, etc. 
     
      OR:
  • Increase the power to 2 ^ 3 times, that is, 2 (double) to the power of 3 = 8. 
         The power of the engine must be 8 times greater with the same surface of the tower
          (verifying the speeds etc.)